漏電保護器誤動作怎么辦?

閱讀次數:811    發布時間: 2021-09-03 14:39:15

?如果發現(xian)漏電(dian)保護器誤動作(zuo),首先(xian)應查明原(yuan)因,然(ran)后予以消除。導致漏電(dian)保護器誤動作(zuo)的原(yuan)因主要有(you)以下幾種(zhong):

(1)、接(jie)線錯誤:因用電設備接(jie)線不(bu)當、相鄰(lin)分支零線相互連接(jie)和漏電保護器極數選擇不(bu)對而引(yin)起(qi)誤動作(zuo)。

(2)、接(jie)地(di)不(bu)當(dang):如零線(xian)重復接(jie)地(di)、自耦變壓(ya)器接(jie)地(di)點分流、零序電流互感器回路(lu)中有金(jin)(jin)屬(shu)管電纜時其金(jin)(jin)屬(shu)管接(jie)地(di)不(bu)當(dang)等引(yin)起誤(wu)動作。

(3)、內(nei)外過電(dian)(dian)壓(ya):當電(dian)(dian)路中(zhong)發(fa)生雷電(dian)(dian)過電(dian)(dian)壓(ya)和操(cao)作過電(dian)(dian)壓(ya)時,由于過電(dian)(dian)壓(ya)頻率(lv)很(hen)高(gao),對地電(dian)(dian)容阻抗很(hen)小(xiao),以致充電(dian)(dian)電(dian)(dian)流很(hen)大,往往引起漏電(dian)(dian)保護器(qi)誤動作。

(4)、電(dian)磁干擾:當漏(lou)電(dian)保護器(qi)附(fu)近有磁性設備接通或(huo)大功率電(dian)器(qi)開合(he)時(shi),所產生的(de)磁場會引起漏(lou)電(dian)保護器(qi)誤動(dong)作(zuo)。在這(zhe)種(zhong)情況(kuang)下,漏(lou)電(dian)保護器(qi)的(de)安裝位置(zhi)應遠離這(zhe)種(zhong)類型的(de)設備。

(5)、環流(liu)影響(xiang):當兩臺(tai)(tai)配電(dian)變壓器(qi)并聯運(yun)行時,如果每臺(tai)(tai)變壓器(qi)的(de)中(zhong)(zhong)性點各有(you)接地線(xian),由于兩臺(tai)(tai)變壓器(qi)的(de)內阻抗不可能完全(quan)相同,接地線(xian)中(zhong)(zhong)會(hui)(hui)出現環流(liu)。若(ruo)環流(liu)很大(da),就會(hui)(hui)引起漏(lou)電(dian)保(bao)護(hu)器(qi)誤(wu)動作。

(6)、水銀燈和熒(ying)光燈回路的影響:當水銀燈或熒(ying)光燈與其鎮流(liu)器(qi)(qi)分開安裝時(shi),由于燈與鎮流(liu)器(qi)(qi)的距(ju)離大,對地(di)(di)電(dian)容(rong)較大,而燈管電(dian)壓又(you)是高(gao)頻(pin)波,對地(di)(di)容(rong)抗(kang)小,因(yin)此(ci)充電(dian)電(dian)流(liu)增(zeng)大。

(7)、工(gong)(gong)作零線(xian)的(de)(de)(de)絕(jue)緣(yuan)電(dian)阻過低(di):如(ru)圖所(suo)示(shi),A分(fen)(fen)支(zhi)和(he)B分(fen)(fen)支(zhi)都(dou)裝有零序電(dian)流(liu)(liu)互感器,B分(fen)(fen)支(zhi)三(san)相負載(zai)平衡(heng),A分(fen)(fen)支(zhi)三(san)相負載(zai)不(bu)平衡(heng),其(qi)零線(xian)上有較(jiao)大的(de)(de)(de)工(gong)(gong)作電(dian)流(liu)(liu)Im流(liu)(liu)過,使工(gong)(gong)作零線(xian)有一定壓降。如(ru)果兩個分(fen)(fen)支(zhi)的(de)(de)(de)零線(xian)對地絕(jue)緣(yuan)電(dian)阻過低(di),則A分(fen)(fen)支(zhi)的(de)(de)(de)零線(xian)工(gong)(gong)作電(dian)流(liu)(liu)的(de)(de)(de)分(fen)(fen)流(liu)(liu)If,經過大地流(liu)(liu)向B分(fen)(fen)支(zhi)回路,此時從兩個漏(lou)電(dian)保(bao)護器上都(dou)能測出漏(lou)電(dian)電(dian)流(liu)(liu)Il,所(suo)以(yi)兩個保(bao)護器都(dou)誤動作。因(yin)此,須重視(shi)工(gong)(gong)作零線(xian)的(de)(de)(de)絕(jue)緣(yuan)水平。

(8)、過(guo)載(zai)和短路(lu)的(de)影響:當漏電(dian)(dian)保(bao)(bao)護(hu)器兼有過(guo)電(dian)(dian)流(liu)(liu)保(bao)(bao)護(hu)、短路(lu)保(bao)(bao)護(hu)時,常因過(guo)電(dian)(dian)流(liu)(liu)短路(lu)保(bao)(bao)護(hu)脫扣器的(de)電(dian)(dian)流(liu)(liu)整定(ding)不當而引(yin)起(qi)漏電(dian)(dian)保(bao)(bao)護(hu)器誤動作(zuo)。為(wei)此,應(ying)重新整定(ding)過(guo)電(dian)(dian)流(liu)(liu)保(bao)(bao)護(hu)裝置的(de)動作(zuo)電(dian)(dian)流(liu)(liu),使(shi)其(qi)與工作(zuo)電(dian)(dian)流(liu)(liu)相匹配。

漏電保護器(qi)因(yin)接線錯(cuo)誤而跳閘的(de)原因(yin)和處理(li)方法

漏電(dian)(dian)(dian)保護(hu)器又叫剩余電(dian)(dian)(dian)流(liu)動作(zuo)(zuo)(zuo)保護(hu)器。通俗(su)些講它(ta)的(de)(de)(de)工作(zuo)(zuo)(zuo)原理通,做(zuo)個(ge)形象點的(de)(de)(de)比喻,火線(xian)(xian)上(shang)的(de)(de)(de)電(dian)(dian)(dian)流(liu),相(xiang)當(dang)于電(dian)(dian)(dian)源流(liu)出(chu)的(de)(de)(de)電(dian)(dian)(dian)流(liu),零線(xian)(xian)上(shang)的(de)(de)(de)電(dian)(dian)(dian)流(liu)相(xiang)當(dang)于流(liu)回(hui)電(dian)(dian)(dian)源的(de)(de)(de)電(dian)(dian)(dian)流(liu),正常不漏電(dian)(dian)(dian)時(shi),流(liu)出(chu)和流(liu)入(ru)電(dian)(dian)(dian)流(liu)大小相(xiang)等,方向相(xiang)反。但當(dang)電(dian)(dian)(dian)路中漏電(dian)(dian)(dian)時(shi),零線(xian)(xian)流(liu)回(hui)的(de)(de)(de)電(dian)(dian)(dian)流(liu)一定小于流(liu)出(chu)的(de)(de)(de)電(dian)(dian)(dian)流(liu),當(dang)這個(ge)電(dian)(dian)(dian)流(liu)差達到漏電(dian)(dian)(dian)保護(hu)器動作(zuo)(zuo)(zuo)電(dian)(dian)(dian)流(liu)時(shi),漏電(dian)(dian)(dian)保護(hu)器就會跳閘。

有(you)很多朋友都問(wen)過同樣一(yi)個問(wen)題,就是有(you)一(yi)臺(tai)設(she)備,接(jie)好線以后,一(yi)送電(dian)運行(xing),它的(de)(de)上一(yi)級漏(lou)電(dian)開關就跳閘,可檢查設(she)備的(de)(de)線路和電(dian)器元件,并沒有(you)破(po)損漏(lou)電(dian)的(de)(de)地方(fang)。為什么會這樣呢(ni)?

其(qi)實就是接線(xian)不正確的(de)原因(yin),這種錯誤往往出現(xian)在(zai)三(san)相(xiang)(xiang)四線(xian)配電系(xi)統(tong)當(dang)中。下面(mian)咱們(men)就講(jiang)一下漏電保護(hu)器在(zai)三(san)相(xiang)(xiang)四線(xian)系(xi)統(tong)中的(de)接線(xian)方法和注意(yi)事項。三(san)相(xiang)(xiang)四線(xian)即地線(xian)、零(ling)線(xian)合一。

出現上述(shu)所說的(de)跳閘情況時,往(wang)往(wang)是將設備電纜(lan)中的(de)四根線直(zhi)接(jie)接(jie)到漏電保護器下火。

漏電保護器

而電纜的(de)另(ling)一(yi)端,設(she)備(bei)操作箱(xiang)內的(de)地線(xian)接(jie)到了操作箱(xiang)金屬外殼接(jie)地端子上。而且(qie)操作箱(xiang)內有220V的(de)用電設(she)備(bei),比(bi)如接(jie)觸(chu)器、指(zhi)示燈、照明燈。這些220V用電設(she)備(bei)的(de)零線(xian)與接(jie)地端子相通。

這樣,操作箱放在地(di)面,或(huo)固定(ding)在鋼結(jie)構上時(shi),操作箱內(nei)220V用(yong)電(dian)設備一工(gong)作,就有一部分電(dian)流通過接地(di)端(duan)子流入大地(di),漏(lou)(lou)電(dian)保護器就會(hui)判定(ding)電(dian)路中漏(lou)(lou)電(dian)而跳閘。

那么(me)正確的接法是(shi)什么(me)呢(ni)?

配電箱

應(ying)該(gai)給設備操作箱另敷設一根地線(xian),如上圖,藍色的零線(xian)接(jie)到(dao)漏電保護器下火N接(jie)線(xian)端(duan)子,黑色的地線(xian)接(jie)到(dao)配(pei)電箱接(jie)地端(duan)子上。

設(she)備(bei)操作(zuo)箱(xiang)的那端,將零(ling)線和(he)地(di)線分(fen)開,零(ling)線接(jie)(jie)藍色線,(220V接(jie)(jie)觸器、指示燈、照(zhao)明燈用到(dao)的線)。保護地(di)線接(jie)(jie)黑線,接(jie)(jie)到(dao)操作(zuo)箱(xiang)外殼接(jie)(jie)地(di)端子,只有這樣接(jie)(jie),設(she)備(bei)才能正常運行。

 

來源:工控教練